ESL10Z3-K Energy Storage Cable

Single-insulated 1000 V DC battery cable, 4 to 150 mm².

ESL10Z3-K Energy Storage Cable
ESL10Z3-K Energy Storage Cable — Cable construction
Cable construction

QC Solar

ESL10Z3-K Energy Storage Cable

  • TÜV
  • 1000 V DC
  • 125 °C
  • Flame retardant

Highly flexible battery energy storage cable to TÜV 2 PfG 2693, rated to 125 °C, for battery racks and inverter connections.

Key features

  • Flexible and easy to install
  • Flame retardant — meets EN 60332-1-2 single vertical flame test
  • Resistant to oil, acid, alkali, water and wear
  • Crack resistant
  • All materials comply with RoHS & REACH

Properties

Conductor
Soft annealed stranded tinned or bare copper (IEC 60228 Class 5)
Insulation
Halogen-free cross-linked polyolefin
Rated voltage
DC 1000 V
Voltage test
AC 4.5 kV, 5 min
Tensile strength
≥ 9 MPa
Elongation at break
≥ 120 %
Working temperature
−40 °C to 125 °C
Colours
Black or orange

Application

Power connection and transmission between system modules such as storage batteries, inverters and the power grid.

Technical data

Cross section (mm²)Conductor (No./mm)Insulation (mm)Cable Ø (mm)Resistance at 20 °C (Ω/km)Weight (kg/km)
4133/0.20.74.1≤ 5.0947
6190/0.20.74.6≤ 3.3966
10323/0.20.75.7≤ 1.95109
16513/0.20.77.3≤ 1.24174
25798/0.20.99.4≤ 0.795276
351121/0.20.910.7≤ 0.565379
501596/0.21.012.6≤ 0.393535
702257/0.21.114.7≤ 0.277749
951887/0.2541.117.3≤ 0.211018
1202368/0.2541.219≤ 0.1641264
1502960/0.2541.421.5≤ 0.1331590

Data from the manufacturer's datasheet. Other sizes, colours and packaging (500 m rolls or 1,000 m reels) on request.